Wire the drive control circuit as shown in Figure 1.

Figure 1. Control Circuit Connection Diagram
1

Connect a 24 V power supply to terminals PS-AC to operate the control circuit while the main circuit power supply is OFF.

2

To set the MFDI power supply (Sinking/Sourcing Mode or internal/external power supply), install or remove a jumper between terminals SC-SP or SC-SN depending on the application.

  • Sinking Mode, Internal power supply: Install the jumper to close the circuit between terminals SC-SP.

  • Sourcing Mode, Internal power supply: Install the jumper to close the circuit between terminals SC-SN.

  • External power supply: Remove the jumper from the MFDI terminals. It is not necessary to close the circuit between terminals SC-SP and terminals SC-SN.

3
4

The maximum output current capacity for terminal +V on the control circuit is 20 mA.

5

DIP switch S1 sets terminal A2 for voltage or current input. The default setting for S1 is current input (“I” side).

6
Do not ground the control circuit terminals AC or connect them to the drive chassis.
7

Do not connect terminals PS and AC inversely. If you connect the wires to the incorrect terminals, it will cause damage to the drive.

8

Set DIP switch S2 to the ON position to enable the termination resistor in the last drive when you use MEMOBUS/Modbus communications.

9

To use the internal power supply with the Safe Disable input, use sourcing mode.

10

Use multi-function analog monitor outputs with analog frequency meters, ammeters, voltmeters, and wattmeters. Do not use monitor outputs with feedback-type signal devices.

11

Jumper S5 sets terminal AM for voltage or current output. The default setting for S5 is voltage output (“V” side).

12

Disconnect the wire jumpers between H1 and HC and H2 and HC to use the Safe Disable input.