When b1-01 = 1 [Frequency Reference Selection 1 = Analog Input], it adds noise to the analog frequency reference during run. Minimize the effects of noise. Change H3-13 [Analog Input FilterTime Constant] to a range of 0.01 s to 0.10 s.