Jump to main content

F3: Digital Input Option

F3 parameters set the type of input signal to use with digital input option card DI-A3.

Use these digital inputs to set the frequency reference when you install the DI-A3 card in a drive. Set b1-01 = 3 [Frequency Reference Selection 1 = Option PCB] to use this card as the frequency reference input. The input signal is isolated input of 24 Vdc and 8 mA.

  • Binary, 16-bit/BCD, 4-digit input

  • Binary, 12-bit/BCD, 3-digit input

  • Binary, 8-bit/BCD, 2-digit input

You can also use the DI-A3 option as an MFDI, if the setting of F3-01 is correct.

On drives with software versions PRG: 01031 and later that do not have a DI-A3 option installed, when you set F3-01 = 8 [Digital Input Function Selection = Multi-Function Digital Input], it enables these functions:

  • H1-40 [Mbus Reg 15C0h bit0 Input Func] to H1-42 [Mbus Reg 15C0h bit2 Input Func]

  • H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]