No.

(Hex.)

Name

Description

Default

(Range)

A1-01

(0101)

RUN

Access Level Selection

Sets user access to parameters. The access level controls which parameters the keypad will display, and which parameters the user can set.

2

(0 - 3)

0
Operation Only

Access to A1-00, A1-01, A1-04 [Password], and the U Monitors.

1
User Parameters

Access to A1-00, A1-01, A1-04, and A2-01 to A2-32 [User Parameters 1 to 32].

2
Advanced Level

Access to all parameters, but not Expert Mode parameters.

3
Expert Level

Access to all parameters including Expert Mode parameters.

Table 1 shows which keypad screens are available for each A1-01 settings.

Table 1. Access Level and Available Keypad Screens

Mode

Keypad Screen

A1-01 [Access Level Selection] Setting

0

1

2

3

Drive Mode

Monitors

Yes

Yes

Yes

Yes

Programming Mode

Parameters

Yes

Yes

Yes

Yes

User Custom Parameters

No

Yes

Yes

Yes

Parameter Backup/Restore

No

No

Yes

Yes

Modified Parameters/Fault Log

No

No

Yes

Yes

Auto-Tuning

No

No

Yes

Yes

Initial Setup Screen

No

No

Yes

Yes

Diagnostic Tools

No

No

Yes

Yes

Note:
  • When you use A1-04 and A1-05 [Password Setting] to set a password, you cannot change the values set in A1-01 to A1-03, A1-06, A1-07,or A2-01 to A2-32.

  • When H1-xx = 1B [MFDI Function Select = Program Lockout], you must activate the terminal to change parameter settings.

  • When you use MEMOBUS/Modbus communications, you must send the Enter command from the controller to the drive and complete the serial communication write process before you can use the keypad to change parameter settings.