No. (Hex.) Name Description Default (Range) A1-01 (0101) RUN Access Level Selection Sets user access to parameters. The access level controls which parameters the keypad will display, and which parameters the user can set. 2 (0 - 3) 0 Operation Only Access to A1-00, A1-01, A1-04 [Password], and the U Monitors. 1 User Parameters Access to A1-00, A1-01, A1-04, and A2-01 to A2-32 [User Parameters 1 to 32]. 2 Advanced Level Access to all parameters, but not Expert Mode parameters. 3 Expert Level Access to all parameters including Expert Mode parameters. Table 1 shows which keypad screens are available for each A1-01 settings. Table 1. Access Level and Available Keypad Screens Mode Keypad Screen A1-01 [Access Level Selection] Setting 0 1 2 3 Drive Mode Monitors Yes Yes Yes Yes Programming Mode Parameters Yes Yes Yes Yes User Custom Parameters No Yes Yes Yes Parameter Backup/Restore No No Yes Yes Modified Parameters/Fault Log No No Yes Yes Auto-Tuning No No Yes Yes Initial Setup Screen No No Yes Yes Diagnostic Tools No No Yes Yes Note: When you use A1-04 and A1-05 [Password Setting] to set a password, you cannot change the values set in A1-01 to A1-03, A1-06, A1-07,or A2-01 to A2-32. When H1-xx = 1B [MFDI Function Select = Program Lockout], you must activate the terminal to change parameter settings. When you use MEMOBUS/Modbus communications, you must send the Enter command from the controller to the drive and complete the serial communication write process before you can use the keypad to change parameter settings.