No. (Hex.) Name Description Default (Range) A1-05 (0105) Password Setting Set the password to lock parameters and prevent changes to parameter settings. Enter the correct password in A1-04 [Password] to unlock parameters and accept changes. 0000 (0000 - 9999) This parameter can lock these parameter settings: A1-01 [Access Level Selection] A1-02 [Control Method Selection] A1-03 [Initialize Parameters] A1-06 [Application Preset] A1-07 [DriveWorksEZ Function Selection] A2-01 to A2-32 [User Parameter 1 to 32] Note: Usually, the keypad will not show A1-05. To show and set A1-05, show A1-04 [Password] and then push and on the keypad at the same time. After you set A1-05, the keypad will not show it again until you enter the correct password in A1-04. Make sure that you remember the A1-05 setting value. If you do not know the A1-05 setting value, contact Yaskawa or your nearest sales representative. When A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization], the drive is initialized to A1-05 = 0000. Be sure to set the password again when a password is necessary for the application. Change the setting value in A1-05 to change the password. The new setting value becomes the new password. When you use the password to unlock and change a parameter, enter a value other than the password in A1-04 to lock the parameter again with the same password. If A1-04 ≠ A1-05, MEMOBUS Communication cannot read or write A1-05.