No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
F1-02
(0381)
|
Encoder Signal Loss Detect Sel
|
       
Sets the method to stop the motor or let the motor continue operating when the drive detects PGo [Encoder (PG) Feedback Loss].
|
1
(0 - 4)
|
If the drive does not detect ouput pulses from the encoder for the time set in F1-14 [Encoder Open-Circuit Detect Time], it will trigger PGo.
Note:
-
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent] faults.
-
In AOLV control, set n4-72 = 1 [Speed Feedback Mode = With Encoder].
- 0
- Ramp to Stop
-
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
- 1
- Coast to Stop
-
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
- 2
- Fast Stop (Use C1-09)
-
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
- 3
- Alarm Only
-
The keypad shows PGo and the drive continues operation. Only use this setting in special conditions to prevent damage to the motor and machinery. The output terminal set for Alarm [H2-01 to H2-04 = 10] activates.
- 4
- No Alarm Display
-
The drive continues operation and does not show PGo on the keypad. Only use this setting in special conditions to prevent damage to the motor and machinery.