No.

(Hex.)

Name

Description

Default

(Range)

b1-04

(0183)

Reverse Operation Selection

Sets the reverse operation function. Disable reverse operation in fan or pump applications where reverse rotation is dangerous.

0

(0, 1)

When reverse operation is prohibited, the drive will not accept a Reverse operation command.

0
Reverse Enabled

The drive will accept a Reverse operation command.

1
Reverse Disabled

The drive will not accept a Reverse operation command.