No.

(Hex.)

Name

Description

Default

(Range)

b3-10

(019A)

Expert

Speed Estimation Detection Gain

Sets the gain to correct estimated frequencies from Speed Estimation Speed Search.

1.05

(1.00 - 1.20)

If the drive detects ov [DC Bus Overvoltage] when you restart the motor, increase the setting value.