No.

(Hex.)

Name

Description

Default

(Range)

b3-14

(019E)

Bi-directional Speed Search

Sets the direction of Speed Search to the direction of the frequency reference or in the motor rotation direction as detected by the drive.

Determined by A1-02, b3-24, and E9-01

(0, 1)

Note:
  • The initial value of b3-14 [Bi-directional Speed Search] is different for different A1-02 [Control Method Selection] settings when you set these parameters: Refer to Parameters that Change from the Default Settings with A1-02 [Control Method Selection] for information.

    • A1-02 = 0, 2, 8 [V/f, OLV, EZOLV]

    • E9-01 = 0 [Motor Type Selection = Induction (IM)]

    • b3-24 = 1 [Speed Search Method Selection = Speed Estimation].

  • The initial value of b3-14 is 0 when you set these parameters:

    • A1-02 = 0, 2, 8

    • E9-01 = 0

    • b3-24 = 2 [Current Detection 2]

  • The initial value of b3-14 is different for different A1-02 settings when you set these parameters: Refer to Parameters that Change from the Default Settings with A1-02 [Control Method Selection] for information.

    • A1-02 = 1, 4, 8 [CL-V/f, AOLV, EZOLV]

    • E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]

  • When you set A1-02, b3-24, and E9-01, set b3-14.

0
Disabled

The drive uses the frequency reference to detect the direction of motor rotation.

1
Enabled

The drive detects the direction of motor rotation during Speed Search.