No.

(Hex.)

Name

Description

Default

(Range)

b3-19

(01F2)

Speed Search Restart Attempts

Sets the number of times to restart Speed Search if Speed Search does not complete.

3 times

(0 - 10 times)

If the drive does the number of Speed Search restarts set in this parameter, it will trigger an SEr [Speed Search Retries Exceeded] error.