No. (Hex.) Name Description Default (Range) F3-01 (0390) Digital Input Function Selection Sets the data format of digital input signals. This parameter is enabled when o1-03 = 0 or 1 [Frequency Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)]. 0 (0 - 8) Note: When o1-03 = 2 [min-1 (r/min) unit] or 3 [User Units], the input signal type is BCD. The o1-03 value sets the setting units. 0 BCD, 1% units 1 BCD, 0.1% units 2 BCD, 0.01% units 3 BCD, 1 Hz units 4 BCD, 0.1 Hz units 5 BCD, 0.01 Hz units 6 BCD (5-digit), 0.01 Hz 7 Binary input The setting unit and setting range are different for different values of F3-03 [Digital Input Data Length Select]. F3-03 = 0 [8-bit]: 100%/255 (-255 to +255) F3-03 = 1 [12-bit]: 100%/4095 (-4095 to +4095) F3-03 = 2 [16-bit]: 100%/30000 (-33000 to +33000) 8 Multi-Function Digital Input The DI-A3 option is also used as a multi-function digital input terminal. When the DI-A3 option is not installed in the drive and F3-01 = 8, these functions are enabled: H1-40 [Mbus Reg 15C0h bit0 Input Func] to H1-42 [Mbus Reg 15C0h bit2 Input Func] H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]