You can use two methods to input the PID feedback value to the drive. Use Single Feedback Signal Use Table 1 to select how the feedback signal is input to the drive for PID control. Table 1. PID Feedback Input Method PID Feedback Input Method Setting Value MFAI terminal A1 Set H3-02 = B [PID Feedback]. MFAI terminal A2 Set H3-10 = B. MFAI terminal A3 Set H3-06 = B. Pulse train input terminal RP Set H6-01 = 1 [PID Feedback Value]. Use Two Feedback Signals and Calculate the Deviation from the Difference between Those Signals Use Table 2 to select how the second feedback value is input to the drive. The drive calculates the deviation of the second feedback value. Set H3-02, H3-06, or H3-10 = 16 [Terminal A1/A3/A2 Function Selection = Differential PID Feedback] to enable the second feedback signal used to calculated the deviation. Table 2. PID Differential Feedback Input Method PID Differential Feedback Input Method Setting Value MFAI terminal A1 Set H3-02 = 16 [Differential PID Feedback]. MFAI terminal A2 Set H3-10 = 16. MFAI terminal A3 Set H3-06 = 16. Note: If you set two or more of H3-02, H3-06, and H3-10 to 16, it will trigger oPE07 [Analog Input Selection Error].