You can use two methods to input the PID feedback value to the drive.

  • Use Single Feedback Signal

    Use Table 1 to select how the feedback signal is input to the drive for PID control.

    Table 1. PID Feedback Input Method

    PID Feedback Input Method

    Setting Value

    MFAI terminal A1

    Set H3-02 = B [PID Feedback].

    MFAI terminal A2

    Set H3-10 = B.

    MFAI terminal A3

    Set H3-06 = B.

    Pulse train input terminal RP

    Set H6-01 = 1 [PID Feedback Value].

  • Use Two Feedback Signals and Calculate the Deviation from the Difference between Those Signals

    Use Table 2 to select how the second feedback value is input to the drive. The drive calculates the deviation of the second feedback value. Set H3-02, H3-06, or H3-10 = 16 [Terminal A1/A3/A2 Function Selection = Differential PID Feedback] to enable the second feedback signal used to calculated the deviation.

    Table 2. PID Differential Feedback Input Method

    PID Differential Feedback Input Method

    Setting Value

    MFAI terminal A1

    Set H3-02 = 16 [Differential PID Feedback].

    MFAI terminal A2

    Set H3-10 = 16.

    MFAI terminal A3

    Set H3-06 = 16.

    Note:

    If you set two or more of H3-02, H3-06, and H3-10 to 16, it will trigger oPE07 [Analog Input Selection Error].