No.

(Hex.)

Name

Description

Default

(Range)

b5-08

(01AC)

RUN

Expert

PID Primary Delay Time Constant

Sets the primary delay time constant for the PID control output. Usually it is not necessary to change this setting.

0.00 s

(0.00 - 10.00 s)

Prevents resonance if there is a large quantity of mechanical friction or if rigidity is unsatisfactory. Set the value larger than the resonant frequency cycle. A value that is too large will decrease drive responsiveness.