No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b8-16
(01F8)
Expert
|
PM E-Save Coefficient Ki
|
       
Sets torque linearity. This parameter uses the Ki value from the motor nameplate. Usually it is not necessary to change this setting.
|
1.00
(0.00 - 3.00)
|
When b8-16 = 1.00 (default), the drive will automatically calculate and control the energy-saving coefficient. If the motor nameplate has a description for “Ki”, set this parameter to the Ki value.
Do this procedure to prevent oscillation when you set b8-01 = 1 [Energy Saving Control Selection = Enabled].
-
Check U5-21 [Energy Save Coeff Ki] and make sure that it aligns with the Ki value on the motor nameplate.
-
If the numbers are different, set b8-16 to the Ki value on the motor nameplate.