No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
b8-20
(0B41)
Expert
|
E-Save Search Width
|
       
Sets the amplitude of Energy-saving control search operations.
|
1.0 degrees
(0.1 - 5.0 degrees)
|
An increase in the value can make the operational efficiency better. However, if the load inertia is small, it may be necessary to adjust the value to prevent machine vibration.
Note:
-
If low inertia causes vibration in the machine, decrease the setting value in 1.0-degree increments and check the response.
-
To make the motor more efficient, increase the setting value in 1.0-degreee increments until the point immediately before machine vibration starts to occur.