No.

(Hex.)

Name

Description

Default

(Range)

b8-20

(0B41)

Expert

E-Save Search Width

Sets the amplitude of Energy-saving control search operations.

1.0 degrees

(0.1 - 5.0 degrees)

An increase in the value can make the operational efficiency better. However, if the load inertia is small, it may be necessary to adjust the value to prevent machine vibration.

Note:
  • If low inertia causes vibration in the machine, decrease the setting value in 1.0-degree increments and check the response.

  • To make the motor more efficient, increase the setting value in 1.0-degreee increments until the point immediately before machine vibration starts to occur.