No.

(Hex.)

Name

Description

Default

(Range)

b8-50

(0B0D)

Standby Mode Selection

Sets the Standby Mode function.

0

(0, 1)

0
Disabled
 
1
Enabled
 

Standby Mode decreases how much power the drive consumes when it is in standby.

Standby Mode waits for the drive to stop, uses the relay output of an MFDO terminal to shut off the input side electromagnetic contactor (MC), then shuts off the main circuit power supply.

Note:

These conditions are also necessary for Standby Mode:

  • Connect an external 24 V power supply.

  • Connect an electromagnetic contactor to the drive input side and connect the MFDO terminal set for H2-xx = 65 [Standby Output]. When the MFDO terminal is OFF, the electromagnetic contactor must be OFF.

  • Frequently starting and stopping the drive and regularly opening and closing the electromagnetic contactor will decrease the service life of the drive.

  • Drive
  • MFDO Terminal
  • External 24 V power supply