F4-02

(0392)

RUN

Terminal V1 Gain

Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output level from the terminal V1 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.

100.0%

(-999.9 - +999.9%)

The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Terminal V1 Signal Level] to set the signal level.

Example settings:

When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage of terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1 outputs a maximum voltage of 10 V.

  • F4-01 [Terminal V1 Function Selection] = 102 (U1-02: Output Frequency)

  • F4-02 = 50.0%

  • F4-05 [Terminal V1 Bias] = 0.0%

  • F4-07 = 0 (0 V to 10 V)