No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
F4-06
(0396)
RUN
|
Terminal V2 Bias
|
       
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.
|
0.0%
(-999.9 - +999.9%)
|
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the signal level.