No.

(Hex.)

Name

Description

Default

(Range)

F6-20

(036B)

MECHATROLINK Station Address

Sets the station address for MECHATROLINK communication. Restart the drive after you change the parameter setting.

0021h

(MECHATROLINK-II: 0020h - 003Fh, MECHATROLINK-III: 0003h - 00EFh)

Note:
  • The setting range changes if using MECHATROLINK-II or MECHATROLINK-III:

    • MECHATROLINK-II (SI-T3) range: 20 to 3F

    • MECHATROLINK-III (SI-ET3) range: 03 to EF

  • Be sure to set a node address that is different than all other node addresses. Incorrect parameter settings will cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.

  • The drive detects AEr errors when the station address is 20 or 3F.