No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
F6-24
(036F)
|
MECHATROLINK Monitor Select (F)
|
       
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive operation control command) and INV_I/O (drive I/O control command). Restart the drive after you change the parameter setting.
|
0000h
(0000h - FFFFh)
|
To enable the MEMOBUS register set in F6-24, set SEL_MON2/1 to 0FH or set SEL_MON3/4 and SEL_MON 5/6 to 0FH. Bytes of the response data enable the MEMOBUS register content that was set F6-24.