C4-01

(0215)

RUN

Torque Compensation Gain

Sets the gain for the torque compensation function. Use this parameter value for motor 1 when operating multiple motors.

Determined by A1-02

(0.00 - 2.50)

Adjust the setting in these control methods and conditions:

 

A1-02 [Control Method Selection]

Status

Adjustment

0 [V/f Control]

1 [V/f Control with Encoder]

8 [EZ Vector Control]

Torque is not sufficient during low-speed operation of 10 Hz or less.

Increase the setting in 0.05-unit increments.

There is vibration in the motor when operating the drive with a light load.

Decrease the setting in 0.05-unit decrements.

The cable between the drive and motor is too long.

Increase the setting in 0.05-unit increments.

Note:
  • Adjust C4-01 to make sure that the output current is not more than the drive rated current during low-speed operation.

  • When A1-02 = 2 [Open Loop Vector], usually it is not necessary to change this setting. If you change this parameter in that control method, it can decrease the torque precision.

  • When A1-02 = 5 [PM Open Loop Vector], usually it is not necessary to change this setting. Setting this value too high can cause overcompensation and motor oscillation.

  • When A1-02 = 8 [EZ Vector Control], you cannot change the setting while the drive is running.