No.

(Hex.)

Name

Description

Default

(Range)

C5-03

(021D)

RUN

ASR Proportional Gain 2

Sets the gain to adjust ASR response.

Determined by A1-02

(0.00 - 300.00)

A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain will cause vibration.