|
No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
C5-32
(0361)
|
Motor 2 Integral Oper at Acc/Dec
|
       
Sets ASR integral operation during acceleration and deceleration for motor 2.
|
0
(0, 1)
|
When it is necessary for the motor speed to be as near the frequency reference as possible during acceleration or deceleration, set this parameter to 1.
Note:
If you enable integral control, overshoot or undershoot can occur when acceleration or deceleration complete. If there are problems with overshooting and undershooting, set this parameter to 0.
- 0
- Disabled
-
Integral operation is not enabled during acceleration or deceleration. Integral operation is always enabled during constant speed.
- 1
- Enabled
-
Integral operation is always enabled.