No.

(Hex.)

Name

Description

Default

(Range)

C5-32

(0361)

Motor 2 Integral Oper at Acc/Dec

Sets ASR integral operation during acceleration and deceleration for motor 2.

0

(0, 1)

When it is necessary for the motor speed to be as near the frequency reference as possible during acceleration or deceleration, set this parameter to 1.

Note:

If you enable integral control, overshoot or undershoot can occur when acceleration or deceleration complete. If there are problems with overshooting and undershooting, set this parameter to 0.

0
Disabled

Integral operation is not enabled during acceleration or deceleration. Integral operation is always enabled during constant speed.

1
Enabled

Integral operation is always enabled.