No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
C6-09
(022B)
|
Carrier Freq at Rotational Tune
|
       
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
|
0
(0, 1)
|
If you set C6-09 = 0 for a high-frequency or low-impedance motor, it can cause oC [Overcurrent]. To prevent oC, set the carrier frequency to a high value and set C6-09 = 1 before you do Auto-Tuning.
The procedure to set the carrier frequency when the A1-02 [Control Method Selection] setting changes.
-
When A1-02 = 2, 3 [OLV, CLV], set C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)] and then increase the value set to C6-03 [Carrier Frequency Upper Limit].
-
When A1-02 = 4 to 7 [AOLV, OLV/PM, AOLV/PM, or CLV/PM], use C6-02 to increase the carrier frequency.
- 0
- 5kHz
-
Note:
When A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, CLV/PM], the carrier frequency is 2 kHz.
- 1
- use C6-03
-
Note:
When A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, CLV/PM], the carrier frequency is as specified in C6-02.