0: 3-Wire Sequence

Setting Value

Function

Description

0

3-Wire Sequence

Sets the direction of motor rotation for 3-wire sequence.

If the 3-wire sequence is set to a terminal that is not MFDI terminals S1 and S2, these terminals will be the input terminals for Forward run/Reverse run command. The drive will automatically set terminal S1 to Run command (RUN) and terminal S2 to Stop command (STOP).

When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2 (Stop command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the drive operates in the forward direction, and when it activates, the drive operates in the reverse direction.

Figure 1. 3-Wire Sequence Wiring Example

.

Figure 2. 3-Wire Sequence Time Chart
Note:
  • To input the Run command, activate the terminal for 1 ms minimum.

  • The default setting for b1-17 [Run Command at Power Up] is 0 [Disregard existing RUN command]. If you enable the Run command on an energized drive, the protective function activates and the [RUN LED] flashes quickly. When the application will let an energized drive Run, set b1-17 = 1 [Accept Existing RUN Command].