1: LOCAL/REMOTE Selection

Setting Value

Function

Description

1

LOCAL/REMOTE Selection

Sets drive control for the keypad (LOCAL) or an external source (REMOTE).

Note:
  • When the MFDI terminal sets the LOCAL/REMOTE selection, [LO/RE Selection Key] on the keypad is disabled.

  • When LOCAL Mode is selected, the green light for [LO/RE LED] comes on.

  • When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.

ON
LOCAL

The keypad is the Frequency reference source and Run command source.

OFF
REMOTE

The frequency reference and Run command settings are set in b1-01, b1-02 [Frequency Reference Selection 1/2] or b1-15, b1-16 [Run Command Selection 1/2].