Jump to main content

2: External Reference 1/2 Selection

Setting Value

Function

Description

2

External Reference 1/2 Selection

Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.

Note:

The ability to switch the Run command source and frequency reference source depends on the setting of b1-07 [LOCAL/REMOTE Run Selection].

Table 1. Ability to Switch the Run Command Source and Frequency Reference Source when Inputting the Run Command

b1-07

Run command source

Frequency reference source

0 [Disregard Existing RUN Command] (Default)

No

Yes

1 [Accept Existing RUN Command]

Yes

Yes

ON
b1-15 [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
 
OFF
b1-01 [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]