Jump to main content

9: Baseblock Command (N.C.)

Setting Value

Function

Description

9

Baseblock Command (N.C.)

Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.

The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the drive will restart the motor and use the speed search function.

ON
Normal operation
 
OFF
Baseblock (drive output stop)