- ON
- Decreases the frequency reference.
-
- OFF
- Holds the current frequency reference.
-
Note:
-
If you set only the Up command or only the Down command, the drive will detect oPE03 [Multi-Function Input Setting Err].
-
If you set two or more of these functions at the same time, the drive will detect oPE03:
-
The Up/Down command does not function in these conditions:
-
b1-01 = 2, 3 [Frequency Reference Selection 1 = Memobus/Modbus Communications, Option PCB]
-
b1-02 ≠ 1 [Run Command Selection 1 ≠ Control Circuit Terminal]
-
Drive is in LOCAL mode
-
Set to b1-15 [Frequency Reference Selection 2] by use of H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
When you enter the UP command, the frequency reference increases. When you enter the Down command, the frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down command, the drive will ignore these frequency references:
-
Frequency reference from Keypad [b1-01 = 0]
-
Frequency reference from Analog Input [b1-01 = 1]
-
Frequency reference from Pulse Train Input [b1-01 = 4]