16: Motor 2 Selection

Setting Value

Function

Description

16

Motor 2 Selection

Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.

You can use an external input to switch operation between two induction motors. The drive will save the control methods, V/f patterns, and motor parameters for the two motors.

ON
Selects motor 2
 
OFF
Selects motor 1
 

When you select motor 2, the drive will switch to motor 2 parameters.

Table 1. Parameters that Switch between Motor 1 and Motor 2

Parameter

Motor 2 Selection

OFF (Motor 1)

ON (Motor 2)

C1-xx [Accel & Decel Time]

C1-01 to C1-04

C1-05 to C1-08

C3-xx [Slip Compensation]

C3-01 to C3-04

C3-21 to C3-24

C4-xx [Torque Compensation]

C4-01

C4-07

C5-xx [Automatic Speed Regulator (ASR)]

C5-01 to C5-08, C5-12, C5-17, C5-18

C5-21 to C5-28, C5-32, C5-37, C5-38

E1-xx, E3-xx [V/f Patterns]

E2-xx, E4-xx [Motor Parameters]

E1-xx, E2-xx

E3-xx, E4-xx

F1-xx [Number of PG Pulses per Revolution]

F1-01 to F1-21

F1-02 to F1-04, F1-08 to F1-11, F1-14, F1-31 to F1-37

Note:
  • When you use 2 motors, the drive applies the protective function set in L1-01 [Motor Overload (oL1) Protection] to motor 1 and motor 2.

  • You cannot switch between motors 1 and 2 during run. If you try to switch motors when they are running, it will cause a rUn [Motor Switch during Run] error.

  • After you switch between encoder motors, you must wait 500 ms minimum to input a Run command. You must wait 200 ms minimum for other control methods.

  • If you set H1-xx = 16 [Motor 2 Selection] and set different control methods in maximum output frequency to motors 1 and 2, the drive will apply the lower of the two maximum to the two motors. The upper limit of d1-xx [Frequency Reference] will change. For example, the upper limit of d1-xx will be 400 when you set these parameters to these values:

    • A1-02 = 2 [Control Method Selection = OLV]

    • E1-04 = 590 [Maximum Output Frequency = 590 Hz]

    • E3-01 = 3 [Motor 2 Control Mode Selection = CLV]

    • E3-04 = 400 [Motor 2 Maximum Output Frequency = 400 Hz]