No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
d4-07
(02AE)
RUN
|
Analog Freq Ref Fluctuate Limit
|
       
If the frequency reference changes for more than the level set to this parameter, then the bias value will be held. The value is set as a percentage of the Maximum Output Frequency.
|
1.0%
(0.1 - 100.0%)
|
Handles frequency reference changes while Up/Down 2 Command [H1-xx = 75, 76] is activated. When the frequency reference changes for more than the level set in d4-07, the drive will hold the bias value, and the drive will accelerate or decelerate to the frequency reference. When the drive is at the frequency reference, it releases the bias hold and the bias follows the Up/Down 2 input commands.
This parameter is applicable only when an analog or pulse input sets the frequency reference.