No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E2-01
(030E)
|
Motor Rated Current (FLA)
|
       
Sets the motor rated current in amps.
|
Determined by o2-04, C6-01
(10% to 200% of the drive rated current)
|
Note:
-
If E2-01 < E2-03 [Motor No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
-
When the drive model changes, the display units for this parameter also change.
-
0.01 A: models 2004 - 2042, 4002 - 4023
-
0.1 A: models 2056 - 2415, 4031 - 4H12
The value set for E2-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter the motor rated current written on the motor nameplate. Auto-Tuning the drive will automatically set E2-01 to the value input for “Motor Rated Current”.