No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E2-03
(0310)
|
Motor No-Load Current
|
       
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-load voltage.
|
Determined by o2-04, C6-01
(0 to E2-01)
|
Note:
When the drive model changes, the display units for this parameter also change.
-
0.01 A: 2004 - 2042, 4002 - 4023
-
0.1 A: 2056 - 2415, 4031 - 4H12
The drive automatically sets this parameter during Auto-Tuning. When you cannot do Auto-Tuning, you can also use the motor no-load current on the motor test report to enter this value manually. Get the test report from the motor manufacturer.
Note:
The default setting of the no-load current is for a 4-pole motor recommended by Yaskawa.