E4-05: Motor 2 Line-to-Line Resistance

No.

(Hex.)

Name

Description

Default

(Range)

E4-05

(0325)

Motor 2 Line-to-Line Resistance

Sets the line-to-line resistance for the motor 2 stator windings.

Determined by o2-04, C6-01

(0.000 - 65.000 Ω)

Note:
  • This value is the motor line-to-line resistance. Do not set this parameter with the resistance per phase.

  • On drive models 4810 to 4H12, the unit is mΩ, and the setting range is 0.000 mΩ to 65.000 mΩ.

Auto-Tuning automatically sets this parameter. If you cannot do Auto-Tuning, use the test report from the motor manufacturer to configure the settings. To calculate the motor line-to-line resistance, use the information shown on the motor nameplate with one of these formulas:

  • E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822

  • B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822

  • F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.728