No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E5-03
(032B)
|
Motor Rated Current (FLA)
|
       
Sets the PM motor rated current (FLA).
|
Determined by E5-01
(10% to 200% of the drive rated current)
|
Note:
The display units are different for different models:
-
0.01 A: models 2004 - 2042, 4002 - 4023
-
0.1 A: models 2056 - 2415, 4031 - 4H12
The drive automatically sets E5-03 to the value input for “PM Motor Rated Current” after you do these types of Auto-Tuning:
-
Manual Entry w/ Motor Data Sheet
-
PM Stationary Auto-Tuning
-
Stationary (R Only)
-
Rotational (Ld, Lq, R, back-EMF)