E9-06: Motor Rated Current (FLA)

No.

(Hex.)

Name

Description

Default

(Range)

E9-06

(11E9)

Motor Rated Current (FLA)

Sets the motor rated current in amps.

Determined by E9-01 and o2-04

(10% to 200% of the drive rated current)

Note:

The display units are different for different models:

  • 0.01 A: models 2004 - 2042, 4002 - 4023

  • 0.1 A: models 2056 - 2415, 4031 - 4H12

The setting value of E9-06 is the reference value for motor protection. Enter the motor rated current written on the motor nameplate. Auto-Tuning the drive will automatically set E9-06 to the value input for “Motor Rated Current”.