No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
E9-06
(11E9)
|
Motor Rated Current (FLA)
|
       
Sets the motor rated current in amps.
|
Determined by E9-01 and o2-04
(10% to 200% of the drive rated current)
|
Note:
The display units are different for different models:
-
0.01 A: models 2004 - 2042, 4002 - 4023
-
0.1 A: models 2056 - 2415, 4031 - 4H12
The setting value of E9-06 is the reference value for motor protection. Enter the motor rated current written on the motor nameplate. Auto-Tuning the drive will automatically set E9-06 to the value input for “Motor Rated Current”.