|
No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L1-01
(0480)
|
Motor Overload (oL1) Protection
|
       
Sets the motor overload protection with electronic thermal protectors.
|
Determined by A1-02
(0 - 6)
|
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply overload protection for the motor:
If the drive detects motor overload, the drive will trigger an oL1 [Motor Overload] and stop the drive output.
Set H2-01 = 1F [Term M1-M2 Function Selection = Motor Overload Alarm (oL1)] to set a motor overload alarm. If the motor overload level is more than 90% of the oL1 detection level, the output terminal activates and triggers an overload alarm.
- 0
- Disable
-
Disable motor protection when motor overload protection is not necessary or when the drive is operating more than one motor.
Refer to Figure 1 for an example of the circuit configuration to connect more than one motor to one drive.
Figure 1. Protection Circuit Configuration to Connect More than One Motor to One Drive
| Notice |
|
When you connect more than one motor to one drive or when the motor amp rating is higher than the drive amp rating, set L1-01 =0 [Motor Overload (oL1) Protection = Disabled] and install thermal overload relays for each motor.
The electronic thermal protection of the drive will not function and it can cause damage to the motor.
|
- 1
- Variable Torque
-
Use this setting for general-purpose motors with a 60 Hz base frequency.
The overload tolerance decreases as motor speed decreases because the cooling fan speed decreases and the ability of the motor to cool decreases in the low speed range.
The overload tolerance characteristics of the motor change the trigger point for the electronic thermal protector. This provides motor overheat protection from low speed to high speed across the full speed range.
|
Load Tolerance
|
Cooling Capability
|
Overload Characteristics
(at 100% motor load)
|
|
This motor is designed to operate with commercial line power. Operate at a 60 Hz base frequency to maximize the motor cooling ability.
|
If the motor operates at frequencies less than 60 Hz, the drive will detect oL1. The drive triggers a fault relay output and the motor coasts to stop.
|
- 2
- Constant Torque 10:1 Speed Range
-
Use this setting for drive-dedicated motors with a speed range for constant torque of 1:10.
The speed control for this motor is 10% to 100% when at 100% load. Operating slower than 10% speed at 100% load will cause motor overload.
|
Load Tolerance
|
Cooling Capability
|
Overload Characteristics
(at 100% motor load)
|
|
This motor is designed to withstand increased temperatures during continuous operation in the low speed range (10% base frequency).
|
The motor operates continuously at 10% to 100% base frequency. Operating slower than 10% speed at 100% load will cause motor overload.
|
- 3
- Constant Torque 100:1 SpeedRange
-
Use this setting for vector motors with a speed range for constant torque of 1:100.
The speed control for this motor is 1% to 100% when at 100% load. Operating slower than 1% speed at 100% load will cause motor overload.
|
Load Tolerance
|
Cooling Capability
|
Overload Characteristics
(at 100% motor load)
|
|
This motor is designed to withstand increased temperatures during continuous operation in the low speed range (1% base frequency).
|
The motor operates continuously at 1% to 100% base frequency. Operating slower than 1% speed at 100% load will cause motor overload.
|
- 4
- PM Variable Torque
-
Use this setting for PM motors with derated torque characteristics.
The overload tolerance decreases as motor speed decreases because the cooling fan speed decreases and the ability of the motor to cool decreases in the low speed range.
The overload tolerance characteristics of the motor change the trigger point for the electronic thermal protector. This provides motor overheat protection from low speed to high speed across the full speed range.
|
Load Tolerance
|
Cooling Capability
|
Overload Characteristics
(at 100% motor load)
|
|
This motor is designed to withstand increased temperatures during continuous operation at rated speed and rated torque.
|
If the motor operates continuously at lower speed than rated rotation speed at more than 100% torque, the drive will detect oL1. The drive triggers a fault relay output and the motor coasts to stop.
|
- 5
- PM Constant Torque
-
Use this setting with a PM motor for constant torque that has a speed range for constant torque of 1:500.
The speed control for this motor is 0.2% to 100% when at 100% load. Operating slower than 0.2% speed at 100% load will cause motor overload.
|
Load Tolerance
|
Cooling Capability
|
Overload Characteristics
(at 100% motor load)
|
|
This motor is designed to withstand increased temperatures during continuous operation in the low speed range (0.2% base frequency).
|
The motor operates continuously at 0.2% to 100% rated speed. Operating slower than 0.2% speed at 100% load will cause motor overload.
|
- 6
- Variable Torque (50Hz)
-
Use this setting for general-purpose motors with a 50 Hz base frequency.
The overload tolerance decreases as motor speed decreases because the cooling fan speed decreases and the ability of the motor to cool decreases in the low speed range.
The overload tolerance characteristics of the motor change the trigger point for the electronic thermal protector. This provides motor overheat protection from low speed to high speed across the full speed range.
|
Load Tolerance
|
Cooling Capability
|
Overload Characteristics
(at 100% motor load)
|
|
This motor is designed to operate with commercial line power. Operate at a 50 Hz base frequency to maximize the motor cooling ability.
|
If the motor operates at frequencies less than commercial line power, the drive will detect oL1. The drive triggers a fault relay output and the motor coasts to stop.
|