L1-02: Motor Overload Protection Time

No.

(Hex.)

Name

Description

Default

(Range)

L1-02

(0481)

Motor Overload Protection Time

Sets the operation time for the electronic thermal protector of the drive to prevent damage to the motor. Usually it is not necessary to change this setting.

1.0 min

(0.1 - 5.0 min)

Set the overload tolerance time to the length of time that the motor can operate at 150% load from continuous operation at 100% load.

When the motor operates at 150% load continuously for 1 minute after continuous operation at 100% load (hot start), the default setting triggers the electronic thermal protector.

Figure 1 shows an example of the electronic thermal protector operation time. Motor overload protection operates in the range between a cold start and a hot start.

This example shows a general-purpose motor operating at the base frequency with L1-02 set to 1.0 min.

  • Cold start

    Shows the motor protection operation time characteristics when the overload occurs immediately after starting operation from a complete stop.

  • Hot start

    Shows the motor protection operation time characteristics when overload occurs from continuous operation below the motor rated current.

Figure 1. Protection Operation Time for a General-purpose Motor at Rated Output Frequency