No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L1-02
(0481)
|
Motor Overload Protection Time
|
       
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the motor. Usually it is not necessary to change this setting.
|
1.0 min
(0.1 - 5.0 min)
|
Set the overload tolerance time to the length of time that the motor can operate at 150% load from continuous operation at 100% load.
When the motor operates at 150% load continuously for 1 minute after continuous operation at 100% load (hot start), the default setting triggers the electronic thermal protector.
Figure 1 shows an example of the electronic thermal protector operation time. Motor overload protection operates in the range between a cold start and a hot start.
This example shows a general-purpose motor operating at the base frequency with L1-02 set to 1.0 min.
-
Cold start
Shows the motor protection operation time characteristics when the overload occurs immediately after starting operation from a complete stop.
-
Hot start
Shows the motor protection operation time characteristics when overload occurs from continuous operation below the motor rated current.
Figure 1. Protection Operation Time for a General-purpose Motor at Rated Output Frequency