Jump to main content

L1-08: oL1 Current Level

No.

(Hex.)

Name

Description

Default

(Range)

L1-08

(1103)

oL1 Current Level

Sets the reference current for the motor 1 thermal overload detection. When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.

0.0 A

(0.0 A or 10% to 150% of the drive rated current)

When L1-08 = 0.0 A, the drive uses E2-01 [Motor Rated Current (FLA)] to detect the motor overload protection. In PM control mode, the drive uses E5-03 [PM Motor Rated Current (FLA)] to detect the motor overload protection.

When L1-08 ≠ 0.0 A, the set value is the reference for motor overload protection.

Note:
  • The display units are different for different models:

    • Models 2004 - 2042, 4002 - 4023: 0.01 A

    • Models 2056 - 2415, 4031 - 4H12: 0.1 A

  • When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.