No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L1-09
(1104)
|
oL1 Current Level for Motor 2
|
       
Sets the reference current for the motor 2 thermal overload detection. When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.
|
0.0 A
(0.0 A or 10 to150% of the drive rated current)
|
When L1-09 = 0.0 A, the drive uses E4-01 [Motor 2 Rated Current] to detect the motor overload protection.
When L1-09 ≠ 0.0 A, the set value is the reference for motor overload protection.
Note:
-
The display units are different for different models:
-
Models 2004 - 2042, 4002 - 4023: 0.01 A
-
Models 2056 - 2415, 4031 - 4H12: 0.1 A
-
When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.