YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
L1-19
(0444)
Expert
NTC Thermistor Disconnect Select
Determines drive operation when the drive detects THo [Thermistor Disconnect].
1
(0 - 3)
The drive ramps to stop in the set deceleration time. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
The keypad shows Tho [Thermistor Disconnect], and the drive continues to operate. The output terminal set to H2-01 to H2-04 = 10 [Alarm] activates.