YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
L3-02
(0490)
Stall Prevent Level during Accel
Sets the output current level to activate the Stall Prevention function during acceleration as a percentage of the drive rated output current.
Determined by C6-01 and L8-38
(0 - 150%)
If you use a motor that is small compared to the drive and the motor stalls, decrease the setting value.
When you operate the motor in the constant power range, set L3-03 [Stall Prevent Limit during Accel].
The upper limit of the setting range changes when C6-01 [Normal / Heavy Duty Selection] changes.
150% when C6-01 = 0 [Heavy Duty Rating].
110% when C6-01 = 1 [Normal Duty Rating].