L3-05
(0493)
|
Stall Prevention during RUN
|
       
Sets the function to enable and disable Stall Prevention During Run.
|
Determined by A1-02
(0 - Determined by A1-02)
|
Stall Prevention function during run prevents the motor from stalling by automatically reducing the speed when an oL1 [Motor Overload] occurs while the motor is running at constant speed.
Note:
-
An output frequency lower than 6 Hz will disable Stall Prevention during Run. The L3-05 and L3-06 [Stall Prevent Level during Run] settings do not have an effect.
-
The setting range changes when A1-02 [Control Method] changes:
-
A1-02 = 0, 1, 5 [V/f, CL-V/f, OLV/PM]: 0 to 2
-
A1-02 = 8 [EZOLV]: 0, 3
- 0
- Disabled
-
The drive runs at the set frequency reference. A heavy load can cause the drive to detect oC [Overcurrent] or oL1 and stall the motor.
- 1
- Deceleration Time 1 (C1-02)
-
The drive will decelerate for the time set in C1-02 [Deceleration Time 1] when the current is more than the Stall Prevention level set in L3-06. When the current level is less than the “L3-06 setting value - 2%” for 100 ms, the drive accelerates again for the acceleration time applicable at that time until it reaches the set frequency.
- 2
- Deceleration Time 2 (C1-04)
-
This setting functions the same as Setting 1 [Deceleration Time 1 (C1-02)]. When the Stall Prevention function is enabled, the drive decelerates with the value set in C1-04 [Deceleration Time 2].
- 3
- Intelligent (Ignore Decel Ramp)
-
Available when A1-02 = 8 [EZOLV]. The drive operates with the largest possible output and prevents motor stalling.