L3-06
(0494)
|
Stall Prevent Level during Run
|
       
Sets the output current level to enable the Stall Prevention function during operation as a percentage of the drive rated output current.
|
Determined by C6-01 and L8-38
(5 - 150%)
|
Note:
-
This parameter is applicable when L3-05 = 1, 2 [Stall Prevention during RUN = Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-04)].
-
When L3-23 = 1 [Stall P Reduction at Constant HP = Automatic Reduction @ CHP Region], the drive will automatically decrease the level in the constant output range.
-
The upper limit of the setting range changes when C6-01 [Normal / Heavy Duty Selection] changes.
Use an Analog Input to Change the Stall Prevent Level during Run
When H3-xx = 8 [MFAI Function Select = Stall Prevent Level During Run], you can change the stall prevention level during run through the input gain and bias settings for terminals A1, A2, and A3.
If you set the input level for terminals A1, A2, and A3 [H3-xx = 8] and L3-06, the drive will use the smaller value for Stall Prevent Level during Run.
Figure 1. Stall Prevention Level during Run with Analog Input