Jump to main content

L3-37: Current Limit P Gain @Accel

No.

(Hex.)

Name

Description

Default

(Range)

L3-37

(11D1)

Expert

Current Limit P Gain @Accel

Suppresses current hunting during acceleration. Usually it is not necessary to change this setting.

5 ms

(0 - 100 ms)

Note:

Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Acceleration] to enable this function.