Jump to main content

L4-06: Frequency Reference @Loss of Ref

No.

(Hex.)

Name

Description

Default

(Range)

L4-06

(04C2)

Frequency Reference @Loss of Ref

Sets the frequency reference as a percentage to continue drive operation after it detects a frequency reference loss. The value is a percentage of the frequency reference before the drive detected the loss.

80.0%

(0.0 - 100.0%)

Set L4-05 = 1 [Fref Loss Detection Selection = Run at (L4-06 x Last Reference)] to enable this parameter.