Jump to main content

L5-05: Auto-Restart Method

No.

(Hex.)

Name

Description

Default

(Range)

L5-05

(0467)

Auto-Restart Method

Sets the count method for the Auto Restart operation.

0

(0, 1)

0
Continuous/Immediate Attempts

Counts the number of successful fault resets through Auto Restart.

When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to stop.

1
Interval/Attempt after L5-04 sec

Counts the number of all fault resets (successful and unsuccessful) through Auto Restart. The drive repeats the Auto Restart process in the intervals set in L5-04 [Interval Method Restart Time].

When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to stop.