Jump to main content

L7-35: Low Freq Regen Torque Limit Lvl

No.

(Hex.)

Name

Description

Default

(Range)

L7-35

(1B57)

Expert

Low Freq Regen Torque Limit Lvl

Sets the torque limit used during low-speed regeneration. Usually it is not necessary to change this setting.

50.0%

(0.0 - 200.0%)

Reduces the regenerative torque limit to the level set with L7-35 when using low frequencies such that the output frequency is less than L7-36 [Regen Torque Limit Derate Freq]. The drive does not decrease torque limits during ramp to stop operation. Decrease the setting of L7-35 when oC [Overcurrent] issues occur while a regenerative load is input and the speed reference is constant.

Note:
  • Reduce the setting value of L7-35 in increments of 10.0% and reduce the setting value of L7-36 in increments of 2.0 Hz when faults occur during regenerative loads at low speed.

  • Setting values that are too high can cause faults.

  • The torque limit reduction function does not operate when L7-35 is set with a value larger than L7-03 [Forward Regenerative Trq Limit] or L7-04 [Reverse Regenerative Trq Limit].

  • The motor may rotate slightly faster than the reference when a regenerative load is input at low speeds while L7-35 is set to a low value.