L7-36: Regen Torque Limit Derate Freq

No.

(Hex.)

Name

Description

Default

(Range)

L7-36

(1B58)

Expert

Regen Torque Limit Derate Freq

Sets the frequency width at which L7-35 [Low Freq Regen Torque Limit Lvl] operates.

6.0 Hz

(0.0 - 30.0 Hz)

If the drive detects oC [Overcurrent] faults when you connect regenerative loads at low speed, increase the setting value. Decreases the torque limit as specified by the setting of L7-35 in a range of 0 ≤ output frequency < L7-36. When the torque limit gradually changes as specified by the output frequency until the output frequency = L7-36, the value changes to the setting of L7-03 [Forward Regenerative Trq Limit] and L7-04 [Reverse Regenerative Trq Limit].

Note:

If you increase the setting of L7-36, the motor will rotate at a speed higher than specified when a you input a regenerative load. Do not set the value higher than necessary.