Jump to main content

L8-01: 3% ERF DB Resistor Protection

No.

(Hex.)

Name

Description

Default

(Range)

L8-01

(04AD)

3% ERF DB Resistor Protection

Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor (3% ED) installed on the heatsink.

0

(0, 1)

0
Disabled

Disables braking resistor protection. Use this setting for dynamic braking options that are not Yaskawa ERF series braking resistors.

1
Enabled

Enables protection for Yaskawa ERF series braking resistors.

Note:

Set L8-01 = 1 and H2-01 to H2-04 = D [MFDO Function Select = Braking Resistor Fault]. Use a sequence to turn OFF power with MFDO.